Permit: T07EL00517

Parcel: 121111090

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/14/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/11/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL LISTED MAST BRACING
2) INSTALL BUSHINGS ON 2" PVC
3) IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD
4) WIRE PANEL IN NEAT AND WORKMAN LIKE MANNER
5) BOND GAS PIPING