Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BOND GAS PIPING ON HOUSE SIDE OF METER |
|
| 06/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND GAS PIPING ON HOUSE SIDE OF METER 2) RECALL AFTER TEP TIE IN |
|
| 06/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING - NEC 230.28 2. GROUND RODS TO BE MIN. 6' APART -- NEC 250.56 3. HAVE BREAKER POSITIONS HIGHER THAN 6'7" - NEC 404.8 4. USE PENETRAX ON ALUMINUM CONNECTIONS 5. CANNOT SEE MARKINGS ON CABLE FOR SIZE & CANNOT SEE MARK ON CABLES ARE SUNLIGHT RESISTANT - NEC 300.8 6. CANNOT VERIFY GAS & WATER BOND - NEC 250.104 7. NEUTRAL CONDUCTORS #6 & SMALLER TO BE CONTINUOUSLY IDENTIFIED PER NEC 200.6 |