Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00513
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/25/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO PROVIDE LADDER FOR INSPECTION 2. NEED BETTER DETAILED PANEL SCHEDULE PER NEC 408.4 3. SERVICE CONDUCTORS CANNOT BE INSTALLED IN SAME RACEWAY WITH OTHER CONDUCTORS. 4. INSTALL SEALING WASHER AT 1/2" EMT CONNECTION TO PANEL FOR UNIT 916 5. SECURE #4 GEC TO BUILDING STRUCTURE 6. NO GEC RUN TO SERVICE FOR UNIT 916 7. NEED TO INSPECT METER SECTION. UNABLE TO INSPECT METERS INSTALLED & SERVICES ENERGIZED PRIOR TO APPROVAL. 8. CANNOT VERIFY WATER BOND 9. CANNOT USE ROMEX IN WET LOCATION 10. REMOVE PAINT FROM GROUND CONNECTIONS AT GAS & WTR PIPES -- NEC 250.12 11. NEED ACCESS TO INTERIOR UNITS TO INSPECT WORK. 12. THIS IS NOT A COMPLETE LIST 13. ELECTRICAL EQUIPMENT TO BE INSTALLED IN NEAT AND WORKMAN LIKE MANNER. |