Permit: T07EL00513

Parcel: 115044580


Addresses:

914 E HELEN ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00513

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/25/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO PROVIDE LADDER FOR INSPECTION
2. NEED BETTER DETAILED PANEL SCHEDULE PER NEC 408.4
3. SERVICE CONDUCTORS CANNOT BE INSTALLED IN SAME RACEWAY WITH OTHER CONDUCTORS.
4. INSTALL SEALING WASHER AT 1/2" EMT CONNECTION TO PANEL FOR UNIT 916
5. SECURE #4 GEC TO BUILDING STRUCTURE
6. NO GEC RUN TO SERVICE FOR UNIT 916
7. NEED TO INSPECT METER SECTION. UNABLE TO INSPECT METERS INSTALLED & SERVICES ENERGIZED PRIOR TO APPROVAL.
8. CANNOT VERIFY WATER BOND
9. CANNOT USE ROMEX IN WET LOCATION
10. REMOVE PAINT FROM GROUND CONNECTIONS AT GAS & WTR PIPES -- NEC 250.12
11. NEED ACCESS TO INTERIOR UNITS TO INSPECT WORK.
12. THIS IS NOT A COMPLETE LIST
13. ELECTRICAL EQUIPMENT TO BE INSTALLED IN NEAT AND WORKMAN LIKE MANNER.