Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/05/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* FINISH #1 OF PREVIOUS INSPECTION |
|
| 04/04/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE FINISH PREVIOUS ITEMS #1, 2, 4 & 5 ALSO, VERIFY DERATING OF CONDUCTORS PER 310.15 *#4 PREVIOUS NO ABBREVIATION AND PERMANENT 408.6 |
|
| 04/03/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NOT ENOUGH BRANCH NEUTRALS 2. #4 GROUND FROM GROUND RODS TO RUN CONTINUOUS & UNSPLICED TO SERVICE PANEL PER 250 NEC 3. TAPE BARE NEUTRAL IN J-BOX 4. I.D ALL CIRCUIT BREAKERS IN PANEL 5. VERIFY PERMIT FOR NEW AC UNIT 6. SHEET METAL TEK NOT APPROVED TO GROUND LUG IN J-BOX --- SCRAP OFF PAINT OR ENAMEL USE NUT & BOLT. |