Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT USE THE NEUTRAL TO GROUND THE J-BOX, EVEN THOUGH ITS BARE IT'S A NEUTRAL NOT AN EQUIPMENT BOND 2. CANNOT USE A BLUE HEAD FOR #4 ALUM 3. CANNOT CONNECT A COPPER TO ALUMINUM TOGETHER BECAUSE THEY ARE DISSIMILAR METALS. 4. SPLIT BOX KEARNEYS USED IN J-BOX MUST HAVE A DIVIDER BETWEEN THEM AND USE MORE TAPE TO WRAP KEARNEYS. 5. A MINERAL OC STRAP CANNOT BE USED ON RISER BRACE THEY OPEN UP. USE CORRECT TYPE 6. STRAP PVC UNDER PANEL 7. USE PROPER METHOD TO GROUND PHONE SYSTEM NOT #10 WIRE UNDER 3/4" 1-HOLE STRAP 8. FIND CORRECT SCREW FOR J-BOX |