Permit: T07EL00499

Parcel: 131112250


Addresses:

5828 E 32ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT USE THE NEUTRAL TO GROUND THE J-BOX, EVEN THOUGH ITS BARE IT'S A NEUTRAL NOT AN EQUIPMENT BOND
2. CANNOT USE A BLUE HEAD FOR #4 ALUM
3. CANNOT CONNECT A COPPER TO ALUMINUM TOGETHER BECAUSE THEY ARE DISSIMILAR METALS.
4. SPLIT BOX KEARNEYS USED IN J-BOX MUST HAVE A DIVIDER BETWEEN THEM AND USE MORE TAPE TO WRAP KEARNEYS.
5. A MINERAL OC STRAP CANNOT BE USED ON RISER BRACE THEY OPEN UP. USE CORRECT TYPE
6. STRAP PVC UNDER PANEL
7. USE PROPER METHOD TO GROUND PHONE SYSTEM NOT #10 WIRE UNDER 3/4" 1-HOLE STRAP
8. FIND CORRECT SCREW FOR J-BOX