Permit: T07EL00490

Parcel: 135090280


Addresses:

7640 E MORELOS PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/19/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) INSTALL PROPER SIZE LUG FOR NEUTRAL TO SUB PANEL
2) INSTALL G.E. BREAKER FOR FEED TO SUB PANEL
3) LABEL BREAKER FOR SUB PANEL
4) INSTALL MAST BRACING PROPERLY. CANNOT USE EMT AND SET SCREW CONNECTORS
5) INSTALL MURRAY BREAKER IN SUB PANEL
6) SEAL OPEN KNOCKOUT IN TOP OF SUB PANEL AND BOTTOM
7) RECALL WHEN CORRECTIONS MADE
04/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
Lock up dogs in the yard.| 910*
1. NO ACCESS TO BACKYARD FOR INSPECTION.
DOGS NEED TO BE LOCKED UP PLEASE