Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. SERVICE DROP TO HAVE PROPER CLEARANCE TO GRADE 2. NEED TO UPGRADE EXISTING MAST, METER BASE AND SERVICE WIRE SO ALL IS 200 AMP RATED 3. SEAL HOLE IN BACK OF PANEL 4. NEED SEALING TYPE LOCKNUTS AND PROPER FITTINGS FOR SIDE ENTRY INTO PANEL 5. NEED NEW AND PROPER TYPE BREAKERS 6. INSTALL MAIN BONDING SCREW 7. TIGHTEN ALL CONNECTIONS 8. CORRECTLY IDENTIFY PANEL DIRECTORY 9. INSTALL GROUND RODS, BOND WATER & GAS PIPES 10. RE-GROUND CATV |
|
| 03/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |