Permit: T07EL00489

Parcel: 113021840


Addresses:

1026 E KING ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/05/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/16/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. SERVICE DROP TO HAVE PROPER CLEARANCE TO GRADE
2. NEED TO UPGRADE EXISTING MAST, METER BASE AND SERVICE WIRE SO ALL IS 200 AMP RATED
3. SEAL HOLE IN BACK OF PANEL
4. NEED SEALING TYPE LOCKNUTS AND PROPER FITTINGS FOR SIDE ENTRY INTO PANEL
5. NEED NEW AND PROPER TYPE BREAKERS
6. INSTALL MAIN BONDING SCREW
7. TIGHTEN ALL CONNECTIONS
8. CORRECTLY IDENTIFY PANEL DIRECTORY
9. INSTALL GROUND RODS, BOND WATER & GAS PIPES
10. RE-GROUND CATV
03/28/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*