Permit: T07EL00474

Parcel: 136332650


Addresses:

9051 E BEECHWOOD PL


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07EL00474

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
06/12/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/06/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MARK SERVICE DISCONNECT PER - NEC 230.70
2. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3
3. BOND NIPPLE BETWEEN METER & PANEL PER - NEC 250.96 AND 250.102
4. BOND WATER & GAS PIPING TO SERVICE PER - NEC 250.104
5. INSTALL CIRCUIT DIRECTORY PER - NEC 408.4
6. INSTALL 2 GROUND RODS MIN. 6' APART PER NEC 250.52, 250.53, 250.56, 250.62, 250.64, 250.66, 250.68, 250.70