Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T07EL00474
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/06/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MARK SERVICE DISCONNECT PER - NEC 230.70 2. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3 3. BOND NIPPLE BETWEEN METER & PANEL PER - NEC 250.96 AND 250.102 4. BOND WATER & GAS PIPING TO SERVICE PER - NEC 250.104 5. INSTALL CIRCUIT DIRECTORY PER - NEC 408.4 6. INSTALL 2 GROUND RODS MIN. 6' APART PER NEC 250.52, 250.53, 250.56, 250.62, 250.64, 250.66, 250.68, 250.70 |