Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPLACE BROKEN RECEPT IN KITCHEN 2. KITCHEN COUNTER RECEPT NEED GFI PROTECTION 3. DOUBLED UP WIRES UNDER 2 POLE G0A BREAKER IN PANEL 4. NEED PROPER OVERCURRENT PROTECTION ON WIRES AT PANEL. 5. BACKFED 2 POLE 100A MAIN NEEDS TO BE BOLTED TO PANEL 6. PROTECT WIRES THROUGH BACK OF PANEL 7. INSTALL WEATHERPROOF BOXES ON OUTDOOR RECEPT. 8. WIRE SWAMP COOLER PROPERLY. NEED CONNECTOR/STRAIN RELIEF ON CORD TO SWAMP COOLER. 9. INSTALL SMOKE DETECOTRS IN BEDROOMS 10.BATHROOM RECEPT NEEDS GFI PROTECTION 11. LABEL CIRCUITS AT PANEL |