Permit: T07EL00469

Parcel: 113042210


Addresses:

826 E HOLAWAY DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/28/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REPLACE BROKEN RECEPT IN KITCHEN
2. KITCHEN COUNTER RECEPT NEED GFI PROTECTION
3. DOUBLED UP WIRES UNDER 2 POLE G0A BREAKER IN PANEL
4. NEED PROPER OVERCURRENT PROTECTION ON WIRES AT PANEL.
5. BACKFED 2 POLE 100A MAIN NEEDS TO BE BOLTED TO PANEL
6. PROTECT WIRES THROUGH BACK OF PANEL
7. INSTALL WEATHERPROOF BOXES ON OUTDOOR RECEPT.
8. WIRE SWAMP COOLER PROPERLY. NEED CONNECTOR/STRAIN RELIEF ON CORD TO SWAMP COOLER.
9. INSTALL SMOKE DETECOTRS IN BEDROOMS
10.BATHROOM RECEPT NEEDS GFI PROTECTION
11. LABEL CIRCUITS AT PANEL