Permit: T07EL00455

Parcel: 106050990

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/22/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SPOKE TO BILL NAVARRO (DNR)
DNR NOT OK WITH CORRECTIONS UNTIL CORRECTIONS PER 3/20/07 IN COMPLIANCE, SEE NOTES PREVIOUS INSPECTIONS, ALSO, DNR TO BE SATISFIED WITH CORRECTIONS - PLEASE NOTIFY JASON JAWORSKY INSPECTION SUPERVISOR
2. BOND WATER PIPE SYSTEM TO GROUND IN SUB-PANEL
03/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. POST ADDRESS ON UNIT
2. SERVICE IN DETERRIORATED CONDITION -- NEEDS UPGRADE
3. AERIAL CONDUCTORS TO BE AS PER 225.18
4. PROTECT NM CABLES ENTERING CONDUITS FROM SHARP EDGES.
5. MISSING LB COVER
6. USE APPROVED FITTING WITH LB - CHASE NIPPLE NOT APPROVED.
7. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE
8. STRUCTURE NEEDS GROUNDING ELECTRODE SYSTEM
9. A MAIN BREAKER IS NEEDED 225.31 & 32
10. LABEL ALL BREAKERS
11. WE HAVE GROUNDED RECEPTACLES ON UNGROUNDED SYSTEM
12. SMOKE DETECTORS NEEDED IN BEDROOM - INSTALL AS PER MANUFACTURES INSTRUCTIONS.
13. BATHROOM NEEDS GFCI RECEPTACLE.