Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/22/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SPOKE TO BILL NAVARRO (DNR) DNR NOT OK WITH CORRECTIONS UNTIL CORRECTIONS PER 3/20/07 IN COMPLIANCE, SEE NOTES PREVIOUS INSPECTIONS, ALSO, DNR TO BE SATISFIED WITH CORRECTIONS - PLEASE NOTIFY JASON JAWORSKY INSPECTION SUPERVISOR 2. BOND WATER PIPE SYSTEM TO GROUND IN SUB-PANEL |
|
| 03/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. POST ADDRESS ON UNIT 2. SERVICE IN DETERRIORATED CONDITION -- NEEDS UPGRADE 3. AERIAL CONDUCTORS TO BE AS PER 225.18 4. PROTECT NM CABLES ENTERING CONDUITS FROM SHARP EDGES. 5. MISSING LB COVER 6. USE APPROVED FITTING WITH LB - CHASE NIPPLE NOT APPROVED. 7. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 8. STRUCTURE NEEDS GROUNDING ELECTRODE SYSTEM 9. A MAIN BREAKER IS NEEDED 225.31 & 32 10. LABEL ALL BREAKERS 11. WE HAVE GROUNDED RECEPTACLES ON UNGROUNDED SYSTEM 12. SMOKE DETECTORS NEEDED IN BEDROOM - INSTALL AS PER MANUFACTURES INSTRUCTIONS. 13. BATHROOM NEEDS GFCI RECEPTACLE. |