Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00452
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. AIRAL CONDUCTORS TO BE 8' ABOVE ROOF 2. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE. 3. MAIN BACK FED BREAKER TO HAVE MANUFACTURES HOLD DOWN. 4. BOND GROUND TO GROUNDED CONDUCTOR 250.24 5. GROUND SWITCHES 6. PROTECT CONDUCTOR INSIDE OF BOX FROM SCREWS. 7. SMOKE DETECTOR NEEDED IN BEDROOM 8. PROTECT CONDUCTORS & CABLES INTO BACK OF JUNCTION BOX & NO SINGLE CONDUCTORS THROUGH ATTIC. 9. VERIFY PERMITS FOR NEW AC UNIT 10. PLEASE TO PERMIT THAT THIS IS UNIT #2 11. KITCHEN RECEPTACLES TO BE GFCI PROTECTED. |