Permit: T07EL00450

Parcel: 123152280


Addresses:

1127 E ADAMS ST #03


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00450

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) SEAL OFF #1 & #6
04/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THE #4 COPPER UFER FROM GROUND RODS TO SERVICE ENCLOSURE IS GROUNDING AND EQUIPMENT GROUND BUS ONLY -- THIS TYPE OF INSTALLATION MUST HAVE A MAIN BONDING JUMPER TO NEUTRAL OR THE #4 COPPER MUST GO TO NEUTRAL DIRECTLY SINCE ITS BONDED TO FRAME.
2. MUST PERMANENTLY MARK OUTSIDE OF PNL 3 AS #3
3. REMOVE GREEN SCREW TO FRAME AT NEUTRAL THIS IS A SUB-PANEL & NEUTRAL TO BE ISOLATED.
04/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO PULL PERMIT FOR 300 AMP SERVICE & FEEDS TO OTHER BUILDINGS.
2. NEED TO PROVIDE ONE LINE DRAWING SHOWING ALL WORK. NEEDS TO SHOW FEEDER SIZES, CONDUIT SIZES AND GROUNDING. DRAWING NEEDS TO BE APPROVED BY PLAN REVIEW.