Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00450
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) SEAL OFF #1 & #6 |
|
04/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE #4 COPPER UFER FROM GROUND RODS TO SERVICE ENCLOSURE IS GROUNDING AND EQUIPMENT GROUND BUS ONLY -- THIS TYPE OF INSTALLATION MUST HAVE A MAIN BONDING JUMPER TO NEUTRAL OR THE #4 COPPER MUST GO TO NEUTRAL DIRECTLY SINCE ITS BONDED TO FRAME. 2. MUST PERMANENTLY MARK OUTSIDE OF PNL 3 AS #3 3. REMOVE GREEN SCREW TO FRAME AT NEUTRAL THIS IS A SUB-PANEL & NEUTRAL TO BE ISOLATED. |
|
04/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO PULL PERMIT FOR 300 AMP SERVICE & FEEDS TO OTHER BUILDINGS. 2. NEED TO PROVIDE ONE LINE DRAWING SHOWING ALL WORK. NEEDS TO SHOW FEEDER SIZES, CONDUIT SIZES AND GROUNDING. DRAWING NEEDS TO BE APPROVED BY PLAN REVIEW. |