Permit: T07EL00445

Parcel: 133262060


Addresses:

409 N SARNOFF DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/30/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VERIFY DERATING FOR ? CURRENT CARRING CONDUCTOR 310.15 & 310.16
2) ALL STRANDS UNDER 30 AMP BREAKER
03/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
FINISH PREVIOUS ITEM 1, 2, 3, 4, 5
03/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. A LISTED BRACE KIT IS TO BE USED
2. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE MATERIAL.
3. PLEASE VERIFY DERATING PER 310.15 & 310.16
4. INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMINALS
5. SUPPORT CONDUIT ON SIDE OF PANEL AND ABOVE JUNCTION BOX AND ACROSS ROOF.
6. ANTI-OXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS.
7. BOND JUNCTION BOX
8. FILL UNUSED OPENINGS IN BOX
03/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
GATES LOCKED
NO ACCESS
NO ONE HOME