Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY DERATING FOR ? CURRENT CARRING CONDUCTOR 310.15 & 310.16 2) ALL STRANDS UNDER 30 AMP BREAKER |
|
| 03/23/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FINISH PREVIOUS ITEM 1, 2, 3, 4, 5 |
|
| 03/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. A LISTED BRACE KIT IS TO BE USED 2. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE MATERIAL. 3. PLEASE VERIFY DERATING PER 310.15 & 310.16 4. INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMINALS 5. SUPPORT CONDUIT ON SIDE OF PANEL AND ABOVE JUNCTION BOX AND ACROSS ROOF. 6. ANTI-OXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS. 7. BOND JUNCTION BOX 8. FILL UNUSED OPENINGS IN BOX |
|
| 03/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* GATES LOCKED NO ACCESS NO ONE HOME |