Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2007 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 03/14/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PLATES ON ALL RECEPTS. 2. INSTALL SMOKE DETECTORS IN ALL BEDROOMS & HALLWAY OUTSIDE BEDROOMS. 3. BATHROOM RECEPT NEED TO BE GFI PROTECTED. 4. INSTALL LIGHT AT 3RD BEDROOM 5. REMOVE TAPPED POWER STRIP FROM LIGHT FIXTURE AT MASTER BATH. 6. FIX WIRE HANGING OUT OF WALL AT OFFICE. 7. INSTALL BOXES ON OPEN SPLICES IN GARAGE. 8. OPEN JUNCTION BOX IN UTILITY ROOM NO CONNECTIONS OR ROMEX PLEASE INSTALL CONNECTORS. 9. IMPROPER GROUNDING AT JUNCTION BOX BACK PORCH. 10. IMPROPER TAP AT LIGHT FIXTURE BACK PORCH 11. PLEASE HAVE ELECTRICAL CONTRACTOR CHECK WIRING THROUGHOUT HOUSE -- TOO MANY VIOLATIONS TO LIST. |