Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/27/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ANSWER AT DOOR 11:00 AM 1. #6 AND SMALLER NEUTRAL TO BE WHITE ENTIRE LENGTH 2. MINIMUM #10 EQUIPMENT GROUND TO AC 3. GROUND J-BOX WITH EQUIPMENT GROUND 4. NEED PROTECTIVE BUSHING #4 & LARGER CONDUCTORS 5. NEED SEALING LOCKNUT FOR RACEWAY INTO SIDE OF PANEL |
|
| 04/06/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) NOTE: WHEN CHANGED TO A SUB-PANEL, SEPERATE GROUNDS AND NEUTRALS |