Permit: T07EL00437

Parcel: 129043150


Addresses:

2002 E 14TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00437

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE NOTES LAST INSPECTION=GROUNDING ELECTRODE SYSTEM MISSING FROM SERVICE
04/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
GROUND WIRE (GROUND ELECTRODE CONDUCTOR)
HAS BEEN REMOVED FROM SERVICE
REPLACE GROUNDING SYSTEM.
03/30/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OBTAIN NECESSARY PERMITS
REPAIR OR REPLACE SYSTEMS FOR AC ON ROOF AS NECESSARY.
03/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ROOF
1. UNSUPPORTED CONDUIT.
2. COOLERS HARD WIRED INTO GUTTED DISCONNECT BOXES
RECEPT. ON ROOF SHOULD BE W/P & COVER
BRING ROOF WIRING UP TO CODE.
3. NO COMPLIANCE WITH NOTES, LAST INSP.
4. AC UNITS NOT PER CODE


USE QUALIFIED ELECTRICIAN TO DO THE WORK.
03/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE RECALL INSPECTION, PROVIDE ROOF LADDER OR LADDER FOR ROOF ACCESS.
2. RESUPPORT RECEPTACLE BOX & CONDUIT BY OUTSIDE ENTRY AT WEST SIDE. ALSO, BOX ON INSIDE OPPOSITE WALL.