Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00437
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES LAST INSPECTION=GROUNDING ELECTRODE SYSTEM MISSING FROM SERVICE |
|
04/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* GROUND WIRE (GROUND ELECTRODE CONDUCTOR) HAS BEEN REMOVED FROM SERVICE REPLACE GROUNDING SYSTEM. |
|
03/30/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OBTAIN NECESSARY PERMITS REPAIR OR REPLACE SYSTEMS FOR AC ON ROOF AS NECESSARY. |
|
03/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ROOF 1. UNSUPPORTED CONDUIT. 2. COOLERS HARD WIRED INTO GUTTED DISCONNECT BOXES RECEPT. ON ROOF SHOULD BE W/P & COVER BRING ROOF WIRING UP TO CODE. 3. NO COMPLIANCE WITH NOTES, LAST INSP. 4. AC UNITS NOT PER CODE USE QUALIFIED ELECTRICIAN TO DO THE WORK. |
|
03/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE RECALL INSPECTION, PROVIDE ROOF LADDER OR LADDER FOR ROOF ACCESS. 2. RESUPPORT RECEPTACLE BOX & CONDUIT BY OUTSIDE ENTRY AT WEST SIDE. ALSO, BOX ON INSIDE OPPOSITE WALL. |