Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPLACE PANEL AS A WHOLE ASSEMBLY - NOT JUST BREAKER BUSS 2. PANEL DIRECTORY TO BE CORRECTLY IDENTIFED 3. USE OXIDE INHIBITOR ON ALL ALUMINUM TERMINATIONS 4. CKT'S NOT TO SHARE BREAKER 5. MAX 15 AMP BREAKER ON 14GA COPPER CONDUCTOR 6. BRITTLE CONDUCTOR INSULATION TO BE PROPERLY REPAIRED/REPLACED -- NOT JUST TAPE. |