Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 03/12/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MARKER PEN NOT APPROVED FOR ADDRESS ON SERVICE MUST BE A PERMANENT LABEL 2. BOND WATER & GAS PIPING TO SERVICE GROUND PER 250 NEC 3. BOND GROUND ON LOAD SIDE OF SERVICE PER 250 NEC 4. THREAD RISER CONDUIT FURTHER INTO HUB AT LEAST 5 THREADS. 5. VERIFY PERMIT FOR NEW AC UNIT |