Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00424
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* THE BOND BUSHING (2") INSIDE THE PANEL WHICH HAS A JUMPER TO PANEL ENCLOSURE NEEDS TO BE A #4 COPPER 250 102C REFERS TO TABLE 250-66 FOR UNPROTECTED 3/0 COPPER -- #4 WIRE NOT #8 |
|
03/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND SERVICE RISER PER NEC 250.92 2. SIZE BOND JUMPER PER NEC 250.102(C) 3. RISER DOES NEED A BONDING BUSHING OR BONDING LOCKNUT PLEASE REFER TO NEC STATED ABOVE 4. SERVICE ENERGIZED WITHOUT APPROVALS. NEED TO SEE BONDING IN METER ENCLOSURE. |
|