Permit: T07EL00410

Parcel: 113043250

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. USE LISTED MAST BRACE, NOT HOMEMADE - NEC 230.28
2. EXPOSE GROUND RODS
3. ALL RACEWAY FITTINGS TO BE TIGHT, AND RACEWAYS ALL THE WAY INTO FITTINGS - NEC 358.42
4. BOND METAL PIPING FOR UNIT #2 TO UNIT #2 SERVICE AND SAME FOR UNIT #1 - NEC 250.104
5. USE PROPER STRAPS TO SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE - NOT WASHERS - NEC 110.3B
6. PANEL DIRECTORY TO BE CORRECTLY IDENTIFIED -
NEC 408.4
7. PROVIDE INTERIOR ACCESS
8. CKT'S IN RACEWAYS TO BE PROPERLY DERATED -
NEC 310.15 B2
9. PROVIDE LADDER FOR INSPECTION
10. MULTI-WIRE BRANCH CKTS WITH SHARED NEUTRAL TO TERMINATE ON SEPARATE PHASES -- NEC 100
11. PANEL DEAD FRONT COVER NOT FITTING PROPERLY?