Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. USE LISTED MAST BRACE, NOT HOMEMADE - NEC 230.28 2. EXPOSE GROUND RODS 3. ALL RACEWAY FITTINGS TO BE TIGHT, AND RACEWAYS ALL THE WAY INTO FITTINGS - NEC 358.42 4. BOND METAL PIPING FOR UNIT #2 TO UNIT #2 SERVICE AND SAME FOR UNIT #1 - NEC 250.104 5. USE PROPER STRAPS TO SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE - NOT WASHERS - NEC 110.3B 6. PANEL DIRECTORY TO BE CORRECTLY IDENTIFIED - NEC 408.4 7. PROVIDE INTERIOR ACCESS 8. CKT'S IN RACEWAYS TO BE PROPERLY DERATED - NEC 310.15 B2 9. PROVIDE LADDER FOR INSPECTION 10. MULTI-WIRE BRANCH CKTS WITH SHARED NEUTRAL TO TERMINATE ON SEPARATE PHASES -- NEC 100 11. PANEL DEAD FRONT COVER NOT FITTING PROPERLY? |