Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE DROP DOES NOT HAVE PROPER CLEARANCE TO GROUND -- NEC 230.24B 2. #6 AND SMALLER NEUTRAL TO BE WHITE ENTIRE LENGTH NEC 200.6 3. IDENTIFY WHITE USED AS HOT @ AC DISCONNECT NEC 200,310 4. A SERVICE RECEPTACLE IS REQUIRED FOR NEW AC -- NEC 210.63 |
|
| 03/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CORRECTLY IDENTIFY NEUTRAL OF OLD 2 WIRE UNGROUNDED SYSTEM. 2. CANNOT USE NEUTRAL FOR BONDING OR GROUNDING |
|
| 03/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |