Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY RAMEY |
|
| 03/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEPARATE GROUNDS AND TERMINATE AS PER MANUFACTURES INSTRUCTIONS. 2. CABLE SHEATHING TO BE 1/4" INTO PANEL. 3. ENTRANCES ABOVE CURRENT CARRING PARTS TO USE AN APPROVED SEALING DEVICE. 4. SUPPORT CONDUIT AS PER CODE. 5. RISE HARDWARE TO BE 1/4" MINIMUM 6. USE A LISTED APPROVED BRACE KIT 7. LABEL BREAKERS AS PER 408.4 - NO ABBREVIATIONS OR GENERAL LABELING. 8. SECURE GROUNDING ELECTRODE CONDUCTOR TO BUILDING. |