Permit: T07EL00395

Parcel: 133261930


Addresses:

201 N SARNOFF DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY RAMEY
03/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEPARATE GROUNDS AND TERMINATE AS PER MANUFACTURES INSTRUCTIONS.
2. CABLE SHEATHING TO BE 1/4" INTO PANEL.
3. ENTRANCES ABOVE CURRENT CARRING PARTS TO USE AN APPROVED SEALING DEVICE.
4. SUPPORT CONDUIT AS PER CODE.
5. RISE HARDWARE TO BE 1/4" MINIMUM
6. USE A LISTED APPROVED BRACE KIT
7. LABEL BREAKERS AS PER 408.4 - NO ABBREVIATIONS OR GENERAL LABELING.
8. SECURE GROUNDING ELECTRODE CONDUCTOR TO BUILDING.