Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - PROGRESS
Permit Number - T07EL00382
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/24/2008 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
08/09/2007 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) MAINTAIN CLEARANCES IN FRONT OF ELECTRICAL EQUIPMENT FOR SAFE ? 110.26 2) RECEIVED LETTER FOR BREAKER SETTINGS |
|
08/02/2007 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. EXPLAINED LACING/LASH OF CONDUCTORS |
|
07/30/2007 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. LASHING/BRACING AS PER MANUFACTURES INSTRUCTIONS 2. RECEIVE GFI TEST & LETTER OF TORQUE |
|
07/16/2007 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. WILL NEED GFI TEST - 230.95 2. PLEASE PROVIDE A LETTER ON COMPANY LETTERHEAD VERIFYING TORQUE OF EQUIPMENT 3. BRACING OF CABLES AS PER MANUFACTURES INSTRUCTIONS 4. FINISH LABELING SERVICE & DISCONNECTS 5. VERIFY BREAKER FAULT AIC |
|
05/07/2007 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK 3/0 TO 2-10' GROUND RODS FOR SERVICE PAD |