Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. W.P BOX ON ROOF OVERFILLED - NEC 314.16 AND NOT PROPERLY GROUNDED - NEC 250.122, 110.12 2. SERVICE NOT SECURE TO WALL - PLASTIC ANCHORS NOT EFFECTIVE - NEC 110.13 3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED - NEC 408.4 |