Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/23/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. A LISTED BRACE KIT IS NEEDED 2. USE AN APPROVED FITTING WITH LB - CHASE NIPPLE NOT APPROVED. 3. SEAL ENTRANCES ABOVE CURRENT CARRING PART WITH AN APPROVED DEVICE. 4. PLEASE VERIFY GAS BOND 5. USE BREAKERS LISTED FOR USE BY MANUFACTURE 6. SUPPORT EQUIPMENT WITH OTHER MEANS THAN DRYWALL SCREWS. 7. TIGHTEN LOOSE FITTINGS 8. IDENTIFY GROUNDED CONDUCTOR 9. VERIFY TEP HEIGHTH AND LOCATION REQUIREMENTS. |