Permit: T07EL00369

Parcel: 110073590


Addresses:

2443 N FAIR OAKS AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/30/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. A LISTED BRACE KIT IS NEEDED
2. USE AN APPROVED FITTING WITH LB - CHASE NIPPLE NOT APPROVED.
3. SEAL ENTRANCES ABOVE CURRENT CARRING PART WITH AN APPROVED DEVICE.
4. PLEASE VERIFY GAS BOND
5. USE BREAKERS LISTED FOR USE BY MANUFACTURE
6. SUPPORT EQUIPMENT WITH OTHER MEANS THAN DRYWALL SCREWS.
7. TIGHTEN LOOSE FITTINGS
8. IDENTIFY GROUNDED CONDUCTOR
9. VERIFY TEP HEIGHTH AND LOCATION REQUIREMENTS.