Permit: T07EL00368

Parcel: 122184090


Addresses:

3549 E BELLEVUE ST

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
04/13/2012 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
03/23/2007 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
03/19/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT RISER WITHIN 3' OF HUB -- 1/4" MINIMUM HARDWARE.
2. A LISTED BRACE KIT IS NEEDED
3. BREAKER TO BE LISTED FOR USE BY MANUFACTURE
4. ADDRESS LABEL TO BE PERMANENT METAL EITHER SCREWED OR RIVITED TO COVER

* A GAS AND WATER BOND WILL BE NEEDED
03/15/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HOT WIRE COMING OUT OF WEATHERHEAD BARE INSULATION HAS BROKEN OFF.

OLD SERVICE EQUIPMENT INADEQUATE TO USE FOR TEMP SERVICE.
03/14/2007 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*