Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1) WALLS CHECKED WIRES OK 2) GROUND BOXES OK 3) SMOKE DETECTORS OK 4) BONDING AND WASHER CIRCUITS OK 5) CALL BACK FOR FINAL |
|
| 05/15/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 2 GROUND RODS NEEDED BOND GAS LINE CUT 2 HOLES TO SEE WIRES CALL BACK FOR REINSPECTION UPGRADE PANEL TO 200 AMPS |
|
| 07/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR ELECTRICAL COVER |
|
| 07/16/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CEILING DRY WALLED BEFORE APPROVAL - OPEN FOR INSPECTION 2. INSTALL NAIL PLATES WHERE HOLE IS LESS THAN 1 1/4" FROM STUD FACE 3. GROUND METAL BOXES 4. SMOKE DETECTORS TO BE MINIMUM 6" DOWN FROM CEILING ON WALL & 36" FROM HVAC VENTS 5. WHERE ARE WASHER/DRYER AND RANGE CKT'S 6. ATTIC ACCESS TO BE 24 X 24 - PROTECT ROMEX WITHIN 6' OF ACCESS 7. YOU WILL NEED TO BOND WATER & GAS PIPES |