Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00364
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/22/2007 | ELECTRIC - FINAL | Partial Approval | ||
| 03/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE TEP FEEDERS TO HOUSE ARE 100 AMPS AT ONE TIME SOMEONE INSTALLED A 200A SERVICE BUT DID NOT COMPLETE 2. 2ND STRUCTURE NOT CONNECTED TO BREAKER AT SERVICE 3. 2ND STRUCUTRE IS REQUIRED TO HAVE ITS OWN GROUNDING SYSTEM PER NEC 2002 250.24 4. SMOKE DETECTORS REQUIRED IN BEDROOMS NOTE: THIS HOUSE USED TO HAVE A 100 AMP SERVICE AS EVIDENT OF POWER LINES TO ROOF FROM TEP, THE SERVICE HAS BEEN CHANGED TO 200 AMPS BUT NEVER COMPLETED, YOU HAVE 100 AMP FEED FROM TEP AND 200 AMP USE AT HOUSE. THE CONNECTIONS ON ROOF HAVE NEVER BEEN FINISHED, YOU NEED AN ELECTRICIAN TO FINISH COMPLETION OK 200 AMP SERVICE |