Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL BUSHINGS ON CONDUITS WITH #4 OR LARGER NEC 352.46 2) INSTALL GROUNDING TO OUT BLDGS PER NEC 250.32 AND NEC 300.3 3) INSTALL DISCONNECTS AT OUT BLDGS PER NEC 225.31 & 225.32 |