Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) CALL FOR FINAL AFTER ROMEX PROTECTED AND TEP TIE IN IS COMPLETE |
|
| 03/12/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. ROMEX MUST BE PROTECTED UP TO ROOF OVERHAND, USE PROPER ROMEX CONNECTORS. 2. USE CONDUIT SLEEVE OR OTHER MEANS TO PROTECT CABLE FROM PHYSICAL DAMAGE. 3. SERVICE NOT PROPERLY GROUNDED, GROUND PER CODE 2 GROUND RODS 6' MIN. APART, BOND WATER & GAS 4. INSTALL BUSHINGS TO PROTECT WIRING EXITING THE BACK OF PANEL. |