Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ADD UNIT # TO PERMIT ADDRESS 2. TIGHTEN WATER BOND CLAMP 3. NEED BUSHING #4 AND LARGER CONDUCTOR 4. J-BOX OVER FILLED, NOT GROUNDED 5. STRAP EMT WITHIN 3' OF BOX 6. HAVE WRONG HUB ON PANEL/NOT RAIN TITE 7. SECURE BOND WIRE TO STRUCTURE - NOT WATER PIPE 8. SHARED NEUTRAL CKTS TO TERMINATE ON SEPARATE PHASES. 9. CONDUCTORS IN J-BOX NICKED/COPPER SHOWING |