Permit: T07EL00345

Parcel: 127050500


Addresses:

4741 E 3RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
04/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BOTH BOXES
04/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio

1. A KO BUSHING DOES NOT SECURE CABLES TO BOXES #7 PREVIOUS INSPECTION.

PLEASE PAY REFEE BEFORE NEXT INSPECTION
03/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FINISH #6 & 7 OF PREVIOUS INSPECTON TO INTERIOR
SUB-PANEL IS AN UNISOLATED NEUTRAL OLD 2-WIRE UNGROUNDED FEEDER.
03/28/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NEED TO VERIFY WIRING METHOD FOR NEW FEEDER INTO SUB-PANEL
03/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BURY GROUNDING ELECTRODE CONDUCTOR
2. USE APPROVED FITTING WITH LB - CHASE NIPPLE NOT APPROVED.
3. MULTIPLE TERMINATIONS UNDER LUG
4. A GUY BACK BRACE WITH A LISTED BRACE KIT MAY BE NEEDED
5. INSTALL LINE SIDE CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS.
6. CANNOT USE NEUTRAL AS A BOND OR GROUND. CORRECTLY IDENTIFY AND RUN A GROUND IN NON-METALLIC RACEWAYS.
7. SECURE CABLES TO BOX 312.5
8. SECURE NON-METALLIC RACEWAYS WITHIN 12" OF BOX OR CONDUITS.
9. TIGHTEN LOOSE FITTINGS.