Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/06/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
| 04/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BOTH BOXES |
|
| 04/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio 1. A KO BUSHING DOES NOT SECURE CABLES TO BOXES #7 PREVIOUS INSPECTION. PLEASE PAY REFEE BEFORE NEXT INSPECTION |
|
| 03/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FINISH #6 & 7 OF PREVIOUS INSPECTON TO INTERIOR SUB-PANEL IS AN UNISOLATED NEUTRAL OLD 2-WIRE UNGROUNDED FEEDER. |
|
| 03/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NEED TO VERIFY WIRING METHOD FOR NEW FEEDER INTO SUB-PANEL |
|
| 03/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BURY GROUNDING ELECTRODE CONDUCTOR 2. USE APPROVED FITTING WITH LB - CHASE NIPPLE NOT APPROVED. 3. MULTIPLE TERMINATIONS UNDER LUG 4. A GUY BACK BRACE WITH A LISTED BRACE KIT MAY BE NEEDED 5. INSTALL LINE SIDE CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS. 6. CANNOT USE NEUTRAL AS A BOND OR GROUND. CORRECTLY IDENTIFY AND RUN A GROUND IN NON-METALLIC RACEWAYS. 7. SECURE CABLES TO BOX 312.5 8. SECURE NON-METALLIC RACEWAYS WITHIN 12" OF BOX OR CONDUITS. 9. TIGHTEN LOOSE FITTINGS. |