Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDUCTORS NOT ALLOWED IN METER SECTION OF SERVICE PER MANUFACTURE 2. INSTALL ALL STRANDS UNDER LUGS 3. USE PROPER HARDWARE FOR SUPPORT - NOT DRYWALL SCREWS. 4. OLD DISCONNECT NOT LISTED OR ALLOWED FOR "J" BOX USE APPROVED BOX 5. SECURE CABLES TO JUNCTION BOX 312.5 6. A LISTED BRACE KIT IS NEEDED |