Permit: T07EL00336

Parcel: 13401009A


Addresses:

425 S BROWN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/19/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE CONDUCTORS SHALL NOT BE INSTALLED IN SAME RACEWAY AS OTHER CONDUCTORS -- NEC 230.7
2. INSTALL BREAKERS LISTED FOR USE IN CUTLER HAMMER PANELS.
3. CONNECT GROUNDING ELECTRODE CONDUCTOR TAP PER NEC 250.64(D)
4. BOND METAL CONDUITS ON LONE SIDE OF SERVICE
PER NEC 250.92
5. ALL STRANDS FROM GROUND WIRE TO BE UNDER TERMINAL
6. STRAP GROUNDING ELECTRODE CONDUCTOR & WTR BOND TO BUILDING STRUCTURE
7. SECURE CONDUITS
8. IDENTIFY GROUNDS PER NEC 250.119
9. CHECK BREAKER SIZE FOR DRYER
10. RECALL WHEN READY