Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE CONDUCTORS SHALL NOT BE INSTALLED IN SAME RACEWAY AS OTHER CONDUCTORS -- NEC 230.7 2. INSTALL BREAKERS LISTED FOR USE IN CUTLER HAMMER PANELS. 3. CONNECT GROUNDING ELECTRODE CONDUCTOR TAP PER NEC 250.64(D) 4. BOND METAL CONDUITS ON LONE SIDE OF SERVICE PER NEC 250.92 5. ALL STRANDS FROM GROUND WIRE TO BE UNDER TERMINAL 6. STRAP GROUNDING ELECTRODE CONDUCTOR & WTR BOND TO BUILDING STRUCTURE 7. SECURE CONDUITS 8. IDENTIFY GROUNDS PER NEC 250.119 9. CHECK BREAKER SIZE FOR DRYER 10. RECALL WHEN READY |