Permit: T07EL00335

Parcel: 121090850

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 100A DISCON. -- ONLY ALLOWED 1/0 CU ONLINE AND LOAD.
2. VERIFY IF SYSTEM IS 120/240V DELTA OR NOT
IF IT IS LABEL DISCONNECT & PANEL AS
PER NEC 2002, 230, 408
03/12/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
FINISH PREVIOUS ITEMS 3 & 5
02/28/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. A LISTED BRACE KIT IS NEEDED AND 1/4" MINIMUM RISER HARDWARE.
2. PREVENT OBJECTIONABLE CURRENT PER 250.6
3. WE NEED AN APPROVED SET OF PLANS
THIS IS NOT A SIMPLE UPGRADE
WHY DO WE HAVE 400 AMPS CONNECTED TO A 200 AMP METER BASE. CONDUCTORS NOT SIZED FOR 400 AMPS
GROUNDING ELECTRODE CONDUCTOR MAY NEED TO BE SIZED PER 250.66
4. LABEL ALL SERVICE EQUIPMENT
5. A PERMIT FOR NEW ELECTRIC FOR NEW SHOP WILL BE NEEDED. THIS SERVICE IS BEING BUILT FOR THAT PURPOSE. NEED TO SEE CONNECTED LOADS.