Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 100A DISCON. -- ONLY ALLOWED 1/0 CU ONLINE AND LOAD. 2. VERIFY IF SYSTEM IS 120/240V DELTA OR NOT IF IT IS LABEL DISCONNECT & PANEL AS PER NEC 2002, 230, 408 |
|
| 03/12/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FINISH PREVIOUS ITEMS 3 & 5 |
|
| 02/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. A LISTED BRACE KIT IS NEEDED AND 1/4" MINIMUM RISER HARDWARE. 2. PREVENT OBJECTIONABLE CURRENT PER 250.6 3. WE NEED AN APPROVED SET OF PLANS THIS IS NOT A SIMPLE UPGRADE WHY DO WE HAVE 400 AMPS CONNECTED TO A 200 AMP METER BASE. CONDUCTORS NOT SIZED FOR 400 AMPS GROUNDING ELECTRODE CONDUCTOR MAY NEED TO BE SIZED PER 250.66 4. LABEL ALL SERVICE EQUIPMENT 5. A PERMIT FOR NEW ELECTRIC FOR NEW SHOP WILL BE NEEDED. THIS SERVICE IS BEING BUILT FOR THAT PURPOSE. NEED TO SEE CONNECTED LOADS. |