Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/16/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REIDENTIFY WHITE WIRE USED AS PHASE CONDUCTOR PER NEC 200.7 2. H O M T SPLIT BREAKERS NOT LISTED FOR USE IN PANEL INSTALL BREAKERS LISTED TO BE USED IN PANEL NEC 110.3 3. INSTALL LISTED MAST BRACING PER NEC 230.28 CANNOT USE EMT WITH MINERALLAC STRAP 4. CANNOT VERIFY GAS & WATER BOND. PLEASE VERIFY. 5. PERMIT DOES NOT COVER NEW CIRCUITS ADDED. NEED TO REVISE PERMIT & PROVIDE DESCRIPTION OF WORK. 6. MAKE UP GROUNDS PROPERLY AT OLD PANEL BOARD CANNOT TERMINATE ALL GROUNDS UNDER ONE LUG. |