Permit: T07EL00333

Parcel: 126162260

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/18/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/16/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REIDENTIFY WHITE WIRE USED AS PHASE CONDUCTOR PER NEC 200.7
2. H O M T SPLIT BREAKERS NOT LISTED FOR USE IN PANEL
INSTALL BREAKERS LISTED TO BE USED IN PANEL NEC 110.3
3. INSTALL LISTED MAST BRACING PER NEC 230.28
CANNOT USE EMT WITH MINERALLAC STRAP
4. CANNOT VERIFY GAS & WATER BOND. PLEASE VERIFY.
5. PERMIT DOES NOT COVER NEW CIRCUITS ADDED. NEED TO REVISE PERMIT & PROVIDE DESCRIPTION OF WORK.
6. MAKE UP GROUNDS PROPERLY AT OLD PANEL BOARD
CANNOT TERMINATE ALL GROUNDS UNDER ONE LUG.