Permit: T07EL00326

Parcel: 11308011A


Addresses:

3156 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00326

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/28/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO USE BLACK UV RATED NYLON TIE WRAPS OUTDOORS - WHITE WILL CRACK.
2. CONDUCTORS ENTERING TOP OF PNL A NEED TO BE PHYSICALLY PROTECTED - COVER WHEN LIFTED UP RUBS AGAINST THEM
3. WEATHERHEAD COVER ON RISER MISSING
4. GROUND WIRE WHICH TIES GROUND BUSHING TO TERMINAL IN MAIN DISCONNECT TO BE TAPED GREEN.

NOTE: THESE GROUND WIRES WILL BE REMOVED AGAIN BECAUSE THEY ARE SO EXPOSED YOU NEED TO RUN THEM IN PVC OR OTHER TYPE OF PHYSICAL PROTECTION IS MAIN GROUND TIED TO NEUTRALS IN BOTH GUTTERS.