Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00321
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2007 | ELECTRIC - FINAL | Approved | ||
05/16/2007 | ELECTRIC - FINAL | Partial Approval | 1. ADDRESS UNITS 2. ATTACH GAS & WATER BOND 3. SCRAPE PAINT OFF LUG IN GUTTER 4. RUN GROUND ELECTRODE CONDUCTOR FROM RODS TO NEUTRAL IN GUTTER. OK TO COVER TRENCH OK TO USE EXISTING GROUNDING SYSTEM AT 2ND BLDG. |
|
05/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE ALL EQUIPMENT TO STRUCTURE, SEVERAL ANCHORS NOT GRABBING -- NEC 110.13A 2. BOND MAST -- NEC 250.96, 250.102 3. IN GUTTER, REMOVE PAINT UNDER LUG & TIGHTEN ALL LUG CONNECTIONS -- NEC 250.12 4. TIGHTEN ALL CONDUCTOR CONNECTIONS THROUGHOUT INCLUDES ACORNS -- NEC 110 5. SECURE G.E.C CONDUCTORS TO STRUCTURE -- NEC 110 6. BOND ALL METAL PIPING -- NEC 250.104 7. INSTALL ADDRESS' AND UNIT #'S ON SERVICES 8. WIRING TO GUEST HOUSE a. RACEWAY TO BE 18" MIN. DEEP -- NEC 300.5 b. GUEST HOUSE WILL NEED SEPARATE GROUNDING ELECTRODE SYSTEM & BONDING -- NEC 250.32 9. ANY NEW BRANCH CKTS OR MECHANICAL TO BE PERMITTED 10. PROVIDE LADDER TO ROOF. |