Permit: T07EL00321

Parcel: 124081600


Addresses:

1305 E 9TH ST #01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00321

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/17/2007 ELECTRIC - FINAL Approved
05/16/2007 ELECTRIC - FINAL Partial Approval 1. ADDRESS UNITS
2. ATTACH GAS & WATER BOND
3. SCRAPE PAINT OFF LUG IN GUTTER
4. RUN GROUND ELECTRODE CONDUCTOR FROM RODS TO NEUTRAL IN GUTTER.

OK TO COVER TRENCH
OK TO USE EXISTING GROUNDING SYSTEM AT 2ND BLDG.
05/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE ALL EQUIPMENT TO STRUCTURE, SEVERAL ANCHORS NOT GRABBING -- NEC 110.13A
2. BOND MAST -- NEC 250.96, 250.102
3. IN GUTTER, REMOVE PAINT UNDER LUG & TIGHTEN ALL LUG CONNECTIONS -- NEC 250.12
4. TIGHTEN ALL CONDUCTOR CONNECTIONS THROUGHOUT INCLUDES ACORNS -- NEC 110
5. SECURE G.E.C CONDUCTORS TO STRUCTURE -- NEC 110
6. BOND ALL METAL PIPING -- NEC 250.104
7. INSTALL ADDRESS' AND UNIT #'S ON SERVICES
8. WIRING TO GUEST HOUSE
a. RACEWAY TO BE 18" MIN. DEEP -- NEC 300.5
b. GUEST HOUSE WILL NEED SEPARATE GROUNDING ELECTRODE SYSTEM & BONDING -- NEC 250.32
9. ANY NEW BRANCH CKTS OR MECHANICAL TO BE PERMITTED
10. PROVIDE LADDER TO ROOF.