Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T07EL00321
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2007 | ELECTRIC - UNDERGROUND | Approved | ||
05/10/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/07/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SERVICE CONDUCTORS, BONDING, GROUNDING ELECTRODE SYSTEM MUST BE IN FOR INSPECTION 2. USE LEAD ANCHORS OR EQUIVALENT FOR MOUNTING ALL EQUIPMENT -- PLASTIC ANCHORS NOT WORKING 3. RACEWAY TO GUEST HOUSE TO BE 18" MINIMUM BELOW GRADE. |