Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE NEUTRAL IN J-BOX TO LEFT OF SERVICE CANNOT BE TIED TO OTHER GROUNDS ITS MAIN PURPOSE TO BE A NEUTRAL NOT A GROUND YOU CAN WIRE OTHER GROUNDS TO ENCLOSURE - BUT RUN INDIVIDUAL NEUTRAL TO SERVICE PNL 2. GROUND WIRE TO RODS APPEARS TO BE A #6 -- NEEDS TO BE A #4 FOR 200A SERVICE 3. ADDRESS SERVICE |