Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2007 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 02/28/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL INSPECTION AFTER TEP TIE IN 2) BOND GAS PIPING ON CUSTOMER SIDE OF METER ( HOUSE SIDE ) |
|
| 02/27/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORTS FOR RISER CONDUIT NOT INSTALLED PROPERLY USE 1/4" MIN. BOLTS, SECURE CONDUIT WITH NO GAPS BETWEEN STRAPS & STRUCTURE. 2. SUPPORT GFI RECEPT. BOX TO WALL 3. STRAP #4 BARE WIRE TO WALL OF H0USE & BOND GAS PIPING BURY #4 4. BUBBLE TYPE COVER REQUIRED FOR GFI OUTLET |
|
| 02/26/2007 | ELECTRIC - SERVICE UPGRADE | Cancelled | CANCELLED PER JIM #909-7048 | |
| 02/26/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |