Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL A LISTED MAST BRACE AND SECURE TO STRUCTURE - NEC 230.28 2. NEUTRAL CONDUCTOR TO SUB-PANEL J-BOX TO BE WHITE NEC 200.6 3. EQUIPMENT GROUNDING CONDUCTOR TO SUB-PANEL J-BOX IS UNDERSIZED - NEC 250.122 4. TIGHTEN BOND CLAMP SCREWS (ALL) |