Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00301
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE PROVIDE A NEW GROUNDING ELECTRODE SYSTEM FOR NEW SERVICE UPGRADE. 2. VERIFY GAS & WATER BONDING 3. OLD PANEL NOT LISTED OR ALLOWED AS A JUNCTION BOX 4. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING CLEAN SURFACE UNDER LUG. 5. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS. 6. CHASE NIPPLE NOT AN APPROVED FITTING WITH LB 7. PROVIDE LOCKABLE MEANS FOR LB'S ON LINE SIDE |