Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/18/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1) IDENTIFY SERVICE DISCONNECT NEC 230.70 B AND INSTALL ADDRESS 2) INSTALL FUSES IN SERVICE DISCONNECT 3) GROUND ELECTRODE/BONDING CONDUCTORS NEED TO BE REPLACED TO EXISTING SERVICE (STOLEN) 4) SINCE USING DISCONNECT AS SERVICE EQUIPMENT, INSTALL REQUIRED NEUTRAL ACCESORY KIT, SEE DISCONNECT LABEL NEC 110.3 B 6) HUB IN TOP OF PANEL TO BE RAINTITE 7) OVER CURRENT PROTECTION TO HIGH TO TRANSFORMER-NEC 450.3 B, ALSO CHECK PRIMARY FEEDERS EQUIPMENT GROUND SIZE |