Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ANSWER AT DOOR PLEASE RECALL AND LEAVE MESSAGE |
|
| 02/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE PROPER SIZE STRAPS TO SECURE BONDING AND GROUNDING ELECTRODE CONDUCTORS TO STRUCTURE NEC 110.12 2. USE WHITE CONDUCTOR FOR NEUTRALL TO 2 GANG W.P J-BOX NEC 200.6 3. USE GREEN OR BARE FOR EQUIPMENT GROUNDS - NEC 250.119A 4. NEED SEALING LOCKNUT FOR SIDE ENTRY RACEWAY - NEC 110 5. IDENTIFY PANEL DIRECTORY ON INSIDE COVER - NEC 408.4 6. SECURE MAST BRACE INTO STRUCTURE (TRUSS) NOT JUST ROOF SHEATHING - NEC 230.28 7. MAKE SURE SERVICE DROP WILL HAVE PROPER CLEARANCE TO GRADE - NEC 230.24B |