Permit: T07EL00293

Parcel: 125160190


Addresses:

3564 E 5TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/28/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ANSWER AT DOOR
PLEASE RECALL AND LEAVE MESSAGE
02/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE PROPER SIZE STRAPS TO SECURE BONDING AND GROUNDING ELECTRODE CONDUCTORS TO STRUCTURE
NEC 110.12
2. USE WHITE CONDUCTOR FOR NEUTRALL TO 2 GANG
W.P J-BOX NEC 200.6
3. USE GREEN OR BARE FOR EQUIPMENT GROUNDS -
NEC 250.119A
4. NEED SEALING LOCKNUT FOR SIDE ENTRY RACEWAY -
NEC 110
5. IDENTIFY PANEL DIRECTORY ON INSIDE COVER - NEC 408.4
6. SECURE MAST BRACE INTO STRUCTURE (TRUSS) NOT JUST ROOF SHEATHING - NEC 230.28
7. MAKE SURE SERVICE DROP WILL HAVE PROPER CLEARANCE TO GRADE - NEC 230.24B