Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* GATE LOCKED |
|
| 11/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED FLASHING FOR MAST 2. CKT'S WITH SHARED NEUTRAL TO TERMINATE ON SEPARATE PHASES 3. GROUND J-BOX 4. SEAL HOLE IN BACK OF PANEL 5. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED 6. BURY G.E.C, WATER BOND CLAMP TO BE ACCESSIBLE |
|
| 06/22/2007 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 06/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAX 15 AMP BREAKER FOR 14 GA HOUSE WIRING 2. USE A LISTED MAST BRACE AND SECURE TO STRUCTURE 3. BOND WATER & GAS PIPES 4. SERVICE LOOSE LOWER LEFT CORNER - DO A BETTER JOB OF SECURING TO HOUSE - NO DRYWALL SCREWS USE LAG BOLTS. 5. CAN'T LOCATE 2ND GROUND ROD WHY ARE RODS SO FAR AWAY? - BURY GROUND WIRE 6. PANEL DIRECTORY NOT CORRECT 7. THREAD RIGID ALL THE WAY INTO HUB 1 1/4 THREAD SHOWING. |