Permit: T07EL00282

Parcel: 113093500


Addresses:

1131 E COPPER ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/15/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
GATE LOCKED
11/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED FLASHING FOR MAST
2. CKT'S WITH SHARED NEUTRAL TO TERMINATE ON SEPARATE PHASES
3. GROUND J-BOX
4. SEAL HOLE IN BACK OF PANEL
5. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED
6. BURY G.E.C, WATER BOND CLAMP TO BE ACCESSIBLE
06/22/2007 ELECTRIC - FINAL Cancelled IVRS - RI canceled
06/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAX 15 AMP BREAKER FOR 14 GA HOUSE WIRING
2. USE A LISTED MAST BRACE AND SECURE TO STRUCTURE
3. BOND WATER & GAS PIPES
4. SERVICE LOOSE LOWER LEFT CORNER - DO A BETTER JOB OF SECURING TO HOUSE - NO DRYWALL SCREWS USE LAG BOLTS.
5. CAN'T LOCATE 2ND GROUND ROD WHY ARE RODS SO FAR AWAY? - BURY GROUND WIRE
6. PANEL DIRECTORY NOT CORRECT
7. THREAD RIGID ALL THE WAY INTO HUB 1 1/4 THREAD SHOWING.