Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING 2. BLANK OPEN BREAKER SLOT IN DEAD FRONT 3. INSTALL PROPER SIZE LUG FOR GROUND ON NEW FEEDER TO EXISTING PANEL. 4. 6/3 ROMEX GOOD FOR 50A REPLACE BREAKER TO 50 A 5. INSPECTED GROUND RODS & BONDING OF WATER/GAS OK |