Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES #1, #3 1. CODE REQUIRES MIN. OF 1/4" OF CABLE SHEATH INTO PANEL ENCLOSURE. 2. GROUND RODS ARE TRIP HAZARD. |
|