Permit: T07EL00262

Parcel: 137054300


Addresses:

759 W IDAHO ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/21/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/20/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) SHEET METAL OR SELF TAPPING SCREW NOT APPROVED FOR GROUNDING IN J-BOX PER 250 NEC-USE BOLT WITH NUT. RECALL WHEN DONE
02/14/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1. INSTALL SEALING LOCKNUTS ON 3/4" CONNECTORS AT TOP OF PANEL.
2. GROUND J-BOX