Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00244
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : EXPOSED SPLICES TO EXISTING FEEDER |
|
04/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ) CALL FOR FINAL INSPECTION AFTER TIE IN |
|
04/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) DOG IN YARD |
|
03/15/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. YOU WILL NEED TO CHANGE DESCRIPTION OF PERMIT TO 100 AMP 2. STRAP #4 BARE TO WALL AT WATER & GAS PIPE BONDING 3. VERIFY #2 RISER CONDUCTORS ARE RATED FOR SUNLITE RESISTANT INSULATION. |